Harmony, 3 phase supply control relay, range 220 to 480 VAC, sequence, phase failure, phase imbalance, voltage
SKU: RM35TF30
Enter your zip code to see prices
Delivery of products may differ based on your Zip code
Simplified panel design due to 1.38in width same as 3-pole circuit breaker
Experience unprecedented accuracy, predictive maintenance, and superior security
Provides automatic shutdown management and fault information for a quick fault identification and troubleshooting
Environmental Data
Harmony Control Relays

Simplified panel design due to 1.38in width same as 3-pole circuit breaker
Experience unprecedented accuracy, predictive maintenance, and superior security
Provides automatic shutdown management and fault information for a quick fault identification and troubleshooting
Transparent cover offers tamper protection and reduces maintenance
Compatible with a wide range of applications, such as hoisting, packaging, lifts, textile, pumping, and water
Harmony Control Monitoring and Control Relays (RM17, RM22, RM35) monitor and detect abnormal operating conditions concerning phase ,current, voltage, frequency, speed, or temperature. The relays inform users of abnormal conditions and allow them to initiate the necessary corrective actions before serious and costly breakdown can occur. Harmony phase control relays detect all possible faults occurring in the phases. Harmony voltage and current control relays ensure your equipment is powered with proper values. Harmony frequency control relay monitors frequency variation from your power generation line. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. Harmony pump control relay controls and protects your pump from dry running or overloading. Harmony speed control relay picks up the improper rhythm of your process. Harmony temperature control relay for lift application is a dedicated to elevator temperature monitoring (EN81). Harmony temperature control relays are dedicated to temperature regulation (heating, cooling or heating/cooling of processes). These Harmony relays are available in 17.5 mm, 22.5 mm or 35 mm wide housings and are DIN rail mounted. Applications for these Harmony relays include hoisting, construction cranes, harbor cranes, packaging, construction elevators, passenger elevators, escalators, textile, water and waste water.
Main
Range of Product
Harmony Control Relays
Relay Type
Multifunction control relay
Product or Component Type
3-phase control relay
Relay name
RM35TF
Relay monitored parameters
Measurement range
220...480 V AC
Time delay type
Adjustable 0.1...10 s, +/- 10 % of the full scale value Tt- time delay upon fault
Output contacts
2 C/O
nominal output current
5 A
Contacts type and composition
2 C/O
[Uc] control circuit voltage
220...480 V
Product Specific Application
For 3-phase supply
Complementary
[Us] rated supply voltage
, self-powered
Supply voltage limits
194…528 V AC, 3 phase
Reset time
1500 ms at 480 V
Maximum switching voltage
Switching capacity in VA
1250 VA
Minimum switching current
10 mA 5 V DC
Maximum switching current
Control circuit voltage limits
- 12 % + 10 % Un
Power consumption in VA
0…22 VA 400 V AC 50 Hz
Voltage detection threshold
< 194 V
Control circuit frequency
50...60 Hz +/- 10 %
Measurement voltage limits
176…528 V AC
Hysteresis
2 %
delay at power up
650 ms
Maximum measuring cycle
140 ms measurement cycle as true rms value
Threshold adjustment voltage
Voltage range
220...480 V phase to phase
Adjustment of asymmetry threshold
5...15 % of Un selected
Repeat accuracy
Measurement error
Response time
< 200 ms (in the event of a fault)
Insulation resistance
[Ui] rated insulation voltage
400 V IEC 60664-1
Supply frequency
50/60 Hz +/- 10 %
Operating position
Any position without derating
Connections - terminals
Tightening torque
5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1
Housing material
Polycarbonate
Local signalling
Mounting support
35 mm symmetrical DIN rail conforming to IEC 60715
Electrical durability
100000 cycles
Mechanical durability
30000000 cycles
Operating rate
<= 360 operations/hour full load
Utilisation category
Safety reliability data
Width
1.4 in (35 mm)
Net Weight
0.29 lb(US) (0.13 kg)
Control Type
Without test button
Environmental footprint
Total lifecycle Carbon footprint
95 kg CO2 eq.
Environmental Disclosure
Product Environmental ProfileCarbon footprint of the manufacturing phase [A1 to A3]
3 kg CO2 eq.
Carbon footprint of the distribution phase [A4]
0 kg CO2 eq.
Carbon footprint of the installation phase [A5]
0 kg CO2 eq.
Carbon footprint of the use phase [B2, B3, B4, B6]
93 kg CO2 eq.
Carbon footprint of the end-of-life phase [C1 to C4]
0.1 kg CO2 eq.
Use Better
Materials and Substances
Packaging made with recycled cardboard
Yes
Packaging without single use plastic
Yes
Pro-active compliance (Product out of EU RoHS legal scope)
REACh Regulation
REACh DeclarationCalifornia proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Use Longer
Lifetime extension
Repair
No
Use Again
Repack and remanufacture
Circularity Profile
End of Life InformationTake-back
No